9-59
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Digital Inputs
Output voltage range
30 V
Galvanic isolation
no
“0” signal
–30 V to +5 V
“1” signal
13 V to 30 V
Permissible zero signal current
at “0” signal
1.5 mA
Typical input current at 24 V
7.3 mA
Digital Outputs
Output voltage range
20 V to 30 V
Galvanic isolation
no
Max. output currents at “1” si-
gnal
100 mA
Short–circuit protector
short–circuit proof
output
Cable length shielded
max. 100 m (330 ft)
Supply Voltage
Logic voltage from 24 V ext.
supply produced with switched
mode power supply
4.7 V to 5.5 V
Current consumption from
24 V supply without outputs
and 24 V sensor
typ. 180 mA