4-4
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
4.1.1 Using the CONFIGURING Screen for ET 200U(DP Siemens)
In the CONFIGURING screen, you assign for each ET 200U(DP Siemens):
the specific modules to specific slots of the slave station
and
the start addresses of the individual modules.
The following steps describe the procedure you must follow to configure
your ET 200U slave station, from creating the configuration data to storing it:
1. Make
the
appropriate
entries in the ET 200 SYSTEM PARAMETERS
screen (
“ET 200 Distributed I/O System” Manual).
After you confirm the ET 200 system parameters with the <F6> (ENTER)
key
2. Press <F8> to return to the FUNCTIONS screen.
3. From the FUNCTIONS screen, press <F2> to go to the CONFIGURING
screen.
Result: The CONFIGURING screen appears.
ENTER
HELP
EXIT
F2
F3
F4
F5
F6
F7
F8
F1
Station number: 3
Program file selected: TEST@@@@ET.200
SIMATIC S5 / COM ET 200
CONFIGURING
Figure 4-1 ET 200U(DP Siemens): CONFIGURING Screen (1)
ET 200U(DP Siemens): Address Assignment,Starting–Up,Diagnosing Faults Using COM ET200