8.4.15
6ES5 456-4UB12 Digital
Output Module
Rated supply voltage L
115 to 230 V AC (47 to 63 Hz)
Number of outputs
8, conditional short-circuit protection
1)
Isolation
Yes, 8 outputs
Range for supply voltage
88 to 264 V AC
Fusing
3.5 A fast, 1 fuse per outputs
Output voltage
for logic 1
for logic 0
L- 1.5 V min.
30 V max.
Residual current at logic 0
5 mA max.
Switching current (resistive, inductive load)
ventilated
not ventilated
40 mA to 2 A;
2)
40 mA to 1 A;
2)
Switching current for lamps
ventilated
not ventilated
40 mA to 2 A;
40 mA to 1 A;
Contactor size
0 (Type 3TB40) to 14 (Type 3TB58) at 230 V AC;
00 (Type 3TJ..) to 8 (Type 3TB52) at 115 V AC;
Max. inrush current for
≤
3 ms
≤
20 ms
≤
50 ms
16 A
8 A
6.5 A
Switching capacity per module
for UL
for CSA
1440 VA max.
2000 VA max.
Permissible line length
300 m max. unshielded
Power supply
Digital section from system bus
5 V, 100 mA typical
Power dissipation (rated operation)
18.0 W
Enable input (F+/F-)
Jumper in front connector
Voltage test to VDE 0160
Between two groups: 2000 V AC
Between group and ground point: 1500 V AC
Mechanical specifications
Dimensions (W x H x D)
40 mm x 255 mm x 195 mm
Weight
Approx. 0.6 kg
1) Protected by a fuse
2) Contactors of Series 3TJ can only be operated at 115 V AC.
8
Specification Sheets for the Modules
System Manual
C79000-B8576-C199-03
8 - 63