Configuring
You must observe the following when configuring systems:
Switching on At the latest 100 ms after power-up of the PLC, the
voltage must be present at the enable inputs of the I/O
modules.
Switching off When the PLC has been switched off, the voltage at
the enable inputs of the I/O modules must still be
present as long as the internal 5 V voltage is present.
Switching off the CC
You should observe the following instructions for switching off CCs
and equipment for supplying power to the enable inputs.
Separate or common
shutdown of the CC/EU and
load power supply
When there is a need to switch off the load power supply separately
without affecting the enabling of modules, there are the following
possibilities for producing the enable voltage. These exist even when
the load power supply is used without an additional capacitor and
common shutdown.
••
230 V AC supply for CC/EU and load power supply
Supply for the enable inputs from:
a) 6ES5 951-4LB11 load power supply
b) Battery
c) Terminals for 24 V on the front plate of the power supply
F +
L +
I/O Modules
230 V AC
CC/EU
-951
a)
c)
b)
Battery
24 V
L +
Power Supply
Load Power Supply
9
The 463 Analog Input Module
System Manual
C79000-B8576-C109-03
9 - 39