5.6
Installing the interface module
Introduction
The interface module connects the ET 200MP with the PROFINET IO/PROFIBUS DP and
exchanges data between the higher-level controller and the I/O modules.
Requirements
The mounting rail is installed.
For a system power supply located to the left of the interface module, a U connector is
inserted on the back left.
Tools required
Screwdriver with 4.5 mm blade
Installing the interface module
Watch video sequence
https://support.industry.siemens.com/cs/media/67462859_installing_web_en/start.htm
To install an interface module, proceed as follows:
1.
Mount the U-connector on the back right-hand side of the interface module.
2.
Hook the interface module on the rail.
3.
Pivot the interface module towards the back.
4.
Tighten the screw for the interface module (torque 1.5 Nm).
Figure 5-7