Wiring
6.5 Wiring rules
Automation system
138
System Manual, 12/2017, A5E03461182-AE
Wiring rules for ...
Power supply element
(screw terminal,
for 35 mm module)
Power supply element
(push-in terminal,
for 25 mm module)
Recommended crimp shape for end sleeve
-
Corresponding to crimping
tool PZ 6/5
* American Wire Gauge
** End sleeve
Permissible cable temperature
Note
Permissible cable temperatures
At the max. ambient temperature of the S7-1500/ET 200MP system, you must select
sufficiently large wire cross-sections so that the permissible cable temperatures are not
exceeded.
Examples:
•
At an ambient temperature of 60° C, a current of, for example, 4 A per wire and a cross-
section of 1.5 mm² Cu, a connecting cable must be rated for a temperature range of at
least 90° C.
•
At an ambient temperature of 60° C, a current of, for example, 2 A per wire and a cross-
section of 1.5 mm² Cu, a connecting cable must be rated for a temperature range of at
least 80° C.