Flexible automation concepts
10.2 Configuration control (option handling)
Automation system
204
System Manual, 12/2017, A5E03461182-AE
Additional information
You can find additional information on configuration control in the section Configuration
control (option handling) (Page 204).
You can find additional information on multiple use IO systems and on configuration control
for IO systems in the PROFINET with STEP 7 V14
http://support.automation.siemens.com/WW/view/en/49948856
) Function Manual.
10.2
Configuration control (option handling)
Introduction
With configuration control (option handling), you handle various standard machine
configuration levels in one project without having to change the hardware configuration or
user program.
Operating principle of configuration control
Configuration control enables you to operate different configuration levels of a standard
machine with a single configuration of the S7-1500 automation system/ET 200MP distributed
I/O system.
●
A station master (maximum configuration) is configured in a project. The station master
comprises all modules needed for all possible equipment components of a modular
standard machine.
●
Provision is made in the user program of the project for various station options for the
different configuration levels of the standard machine and for selection of a station option.
A station option uses, for example, only some of the modules of the station master and
these modules are not inserted in the configured order.
●
Manufacturers of standard machines select a station option for a configuration level of the
standard machine. They do not have change the project or download the modified
configuration.
You use a control data record you have programmed to notify the CPU/interface module as
to which modules are missing or located on different slots in a station option as compared to
the station master. The configuration control has no effect on the parameter assignment of
the modules.
The configuration control allows you to flexibly vary the centralized/distributed configuration.
As a precondition for this, the station option must be able to be derived from the station
master.