Commissioning
11.4 Procedure for commissioning the ET 200MP distributed I/O system
Automation system
230
System Manual, 12/2017, A5E03461182-AE
11.4
Procedure for commissioning the ET 200MP distributed I/O system
11.4.1
Commissioning the ET 200MP for PROFINET IO
Introduction
The commissioning of your automation system depends on the plant configuration.
The following procedure describes the commissioning of the distributed I/O system on an IO
controller.
Commissioning procedure
To commission the ET 200MP as an IO device for PROFINET IO, we recommend the
following procedure:
Table 11- 2 Procedure for commissioning the ET 200MP as an IO device for PROFINET IO
Step
Procedure
See...
1
Install ET 200MP
Section Installation
(Page 108)
2
Connect ET 200MP
•
Supply voltages
•
PROFINET IO
•
Sensors and actuators
4
Configure IO controller
CPU manual or documenta-
tion of the IO controller
5
Switch on supply voltages for the IO controller
CPU manual or documenta-
tion of the IO controller
6
Switch on supply voltages for IO devices
Interface module
) manual
7
Download configuration to the IO controller
STEP 7 online help
8
Switch IO controller to RUN mode
CPU manual or documenta-
tion of the IO controller
9
Check LEDs
Interface module
) manual
10
Test inputs and outputs
The following functions are
helpful: Monitoring and modi-
fying tags, testing with pro-
gram status, forcing,
modifying the outputs. See
section Test functions and
fault resolution (Page 302)