Commissioning
11.4 Procedure for commissioning the ET 200MP distributed I/O system
Automation system
System Manual, 12/2017, A5E03461182-AE
231
Note
The operating mode transitions for the IO controller from RUN to STOP or from STOP to
RUN can take several milliseconds, until the mode transition for the inputs and outputs of all
I/O modules for the ET 200MP station is completed. This delay also applies to isochronous
mode.
11.4.2
Commissioning the ET 200MP for PROFIBUS DP
Introduction
The commissioning of your automation system depends on the plant configuration.
The following procedure describes the commissioning of the ET 200MP distributed I/O
system on a DP master.
Commissioning procedure
To commission the ET 200MP as a DP slave for PROFIBUS DP, we recommend the
following procedure:
Table 11- 3 Procedure for commissioning the ET 200MP as a DP slave for PROFIBUS DP
Step
Procedure
See...
1
Install ET 200MP (with IM 155-5 DP ST)
Section Installation
(Page 108)
2
Set the PROFIBUS address on the interface module
Manual for the interface mod-
ule
3
Connect ET 200MP
•
Supply voltages
•
PROFIBUS DP
•
Sensors and actuators
4
Configure DP master (including PROFIBUS address) Documentation of the DP
master
5
Switch on supply voltages for DP master
Documentation of the DP
master
6
Switch on supply voltages for DP slaves
Interface module
) manual
7
Download configuration to the DP master
STEP 7 online help