Commissioning
11.7 Backing up and restoring the CPU configuration
Automation system
244
System Manual, 12/2017, A5E03461182-AE
11.7
Backing up and restoring the CPU configuration
Backup from online device
You will make a number of changes to your plant over time, for example, add new devices,
replace existing devices or adapt the user program. If these changes result in undesirable
behavior, you can restore the plant to an earlier state. Before you load a changed
configuration to the CPU, first use the option "Backup from online device" to create a
complete backup of the current device status.
Upload from device (software)
With the option "Upload from device (software)", you load the software project data from the
CPU to an existing CPU in the project.
Upload device as new station
If you are operating a new programming device/PC in the plant, the STEP 7 project that was
used to create the plant configuration might not be available. In this case you can use the
option "Upload device as new station" to load the device's data into a project in your PG/PC.
Snapshot of the monitor values
You can use the option "Snapshot of the monitor values" to backup the current values of the
data block, in order to be able to restore the current values if necessary at a later date.
Overview of backup types
The table below shows the backup of CPU data depending on the selected type of backup
and its specific characteristics:
Backup from online
device
Upload from device
(software)
Upload device as
new station
Snapshot of the
monitor values
Actual values of all DBs
(global and instance data blocks)*
✓
✓
✓
✓
Blocks of the type OB, FC, FB and
DB
✓
✓
✓
--
PLC tags
(tag names and constant names)
✓
✓
✓
--
Technology objects
✓
✓
✓
--
Hardware configuration
✓
--
✓
--
Actual values (bit memories, tim-
ers, counters)*
✓
--
--
--
Contents of the SIMATIC memory
card
✓
--
--
--
Archives, recipes
✓
--
--
--
Entries in the diagnostics buffer
--
--
--
--
Current time
--
--
--
--
Properties of the type of backup
Backup possible for fail-safe CPUs
✓
--
--
✓
Backup can be edited
--
✓
✓
✓
Backup possible in operating mode
STOP
RUN, STOP
RUN, STOP
RUN, STOP
* Only the values of the tags that are set as retentive are backed up
Summary of Contents for Simatic S7-1500/ET 200MP