Commissioning
11.9 Identification and maintenance data
Automation system
System Manual, 12/2017, A5E03461182-AE
253
Procedure for reading I&M data via STEP 7
Requirement: There must be an online connection to the CPU/interface module.
To read I&M data using STEP 7, follow these steps:
1.
In the project tree, select the CPU/interface module and go to "Online & diagnostics".
2.
In the "Diagnostics" folder, select the "General" area.
Procedure for entering maintenance data via STEP 7
STEP 7 assigns a default module name. You can enter the following information:
●
Plant designation (I&M 1)
●
Location identifier (I&M 1)
●
Installation date (I&M 2)
●
Additional information (I&M 3)
To enter maintenance data via STEP 7, follow these steps:
1.
In the device view of STEP 7, select the CPU/interface module or a module.
2.
In the properties under "General", select the "Identification & Maintenance" area and
enter the data.
During the loading of the hardware configuration, the maintenance data (I&M 1, 2, 3) are
also loaded.
Procedure for reading I&M data via the Web server
The procedure is described in detail in the Web server Function Manual