Commissioning
11.9 Identification and maintenance data
Automation system
System Manual, 12/2017, A5E03461182-AE
255
Identification data
Access
Example
Explanation
•
IM_SWRevision_Internal_
Change
(1 byte)
0000
H
- 00FF
H
IM_REVISION_COUNTER
read (2 bytes)
0000
H
Provides information about parameter
changes on the module
(not used)
IM_PROFILE_ID
read (2 bytes)
0000
H
Generic Device
IM_PROFILE_SPECIFIC_TYPE read (2 bytes)
0001
H
CPU
0003
H
I/O modules
IM_VERSION
read
0101
H
Provides information on the ID data ver-
sion
(0101
H
= Version 1.1)
•
IM_Version_Major
(1 byte)
•
IM_Version_Minor
(1 byte)
IM_SUPPORTED
read (2 bytes)
000E
H
provides information about the available
identification and maintenance data
(I&M1 to I&M3)
Maintenance data 1: (Record index AFF1
H
)
IM_TAG_FUNCTION
read/write (32
bytes)
-
Enter an identifier for the module here,
that is unique plant-wide.
IM_TAG_LOCATION
read/write (22
bytes)
-
Enter the installation location of the
module here.
Maintenance data 2: (Record index AFF2
H
)
IM_DATE
read/write (16
bytes)
YYYY-MM-DD HH:MM
Enter the installation date of the module
here.
Maintenance data 3: (Record index AFF3
H
)
IM_DESCRIPTOR
read/write (54
bytes)
-
Enter a comment about the module here.
Reading I&M records with record 255 (distributed configuration via PROFIBUS)
Use Read data record ("RDREC" instruction) to access specific identification data.
The modules support standardized access to identification data using DR 255 (index 65000
to 65003). For additional information on the DR 255 data structure, refer to the specifications
of the Profile Guidelines Part 1: Identification & Maintenance Functions - Order no.: 3.502,
Version 1.2, October 2009.