Test functions and fault resolution
15.2 Reading out/saving service data
Automation system
310
System Manual, 12/2017, A5E03461182-AE
Procedure using the Web server
To read service data using the Web server, follow these steps:
1.
Open a web browser that is suitable for communication with the CPU.
2.
Enter the following address in the address bar of the web browser:
https://<CPU IP address>/save_service_data, e.g. https://172.23.15.3/save_service_data
3.
The service data page will appear on your screen, with a button for saving the service
data.
Figure 15-1 Reading out service data via the web server
4.
Save the service data locally on your PC/programming device, by clicking "Save
ServiceData".
Result: The data is saved in a .dmp file with the following naming convention: <Article
number> <Serial number> <Time stamp>.dmp". You can change the file name.
Note
If you have defined your user page as the home page of the Web server, direct access to the
service data by inputting the IP address of the CPU is not possible. For more information on
reading out service data via a user-defined page, refer to the Web server
http://support.automation.siemens.com/WW/view/en/59193560
) function manual.
Procedure using STEP 7
A description of how to save service data is available under the keyword "Save service data"
in STEP 7 online help.