Technical specifications
16.4 Shipping and storage conditions
Automation system
322
System Manual, 12/2017, A5E03461182-AE
16.4
Shipping and storage conditions
Introduction
The S7-1500 automation system / ET 200MP I/O system meet the specifications regarding
transport and storage conditions pursuant to IEC 61131-2. The following information applies
to modules that are shipped and/or stored in their original packaging.
Shipping and storage conditions for modules
Table 16- 6 Shipping and storage conditions
Type of condition
Permissible range
Free fall (in shipping package)
≤
1 m
Temperature
from -40 °C to +70 °C
Barometric pressure
from 1140 to 660 hPa (corresponds to an eleva-
tion of -1000 to 3500 m)
Relative humidity
5% to 95%, without condensation
Sinusoidal vibrations in accordance with IEC
60068-2-6
5 - 9 Hz: 3.5 mm
9 - 500 Hz: 9.8 m/s
2
Shock in accordance with IEC 60068-2-27
250 m/s
2
, 6 ms, 1000 shocks
Summary of Contents for Simatic S7-1500/ET 200MP