Technical specifications
16.5 Mechanical and climatic ambient conditions
Automation system
System Manual, 12/2017, A5E03461182-AE
323
16.5
Mechanical and climatic ambient conditions
Operating conditions
The S7-1500 automation system/ET 200MP distributed I/O system is suitable for use in
weather-proof, fixed locations. The operating conditions are based on the requirements of
DIN IEC 60721-3-3:
●
Class 3M3 (mechanical requirements)
●
Class 3K3 (climatic requirements)
Test of mechanical ambient conditions
The table below provides important information with respect to the type and scope of the test
of ambient mechanical conditions.
Table 16- 7 Test of mechanical ambient conditions
Condition tested
Test Standard
Comment
Vibration
Vibration test accord-
ing to IEC 60068-2-6
(Sinus)
Type of oscillation: Frequency sweeps with a rate of change of 1 oc-
tave/minute.
5 Hz
≤
f
≤
8.4 Hz, constant amplitude 7 mm
8.4 Hz
≤
f
≤
150 Hz, constant acceleration 2 g
Duration of oscillation: 10 frequency sweeps per axis, along each of the 3
mutually perpendicular axes
Shock
Shock, tested accord-
ing to IEC 60068-2-27
Type of shock: Half-sine
Shock intensity: 15 g max., duration 11 ms
Direction of shock: 3 shocks each in (+/-) direction, along each of the 3
mutually perpendicular axes
Continuous shock
Shock, tested accord-
ing to IEC 60068-2-27
Type of shock: Half-sine
Shock intensity: 250 m/s
2
peak value, 6 ms duration
Direction of shock: 1000 shocks each in (+/-) direction, along each of the
3 mutually perpendicular axes
Summary of Contents for Simatic S7-1500/ET 200MP