Technical specifications
16.5 Mechanical and climatic ambient conditions
Automation system
324
System Manual, 12/2017, A5E03461182-AE
Reduction of vibrations
If your S7-1500 automation system/ET 200MP distributed I/O system is exposed to severe
shock or vibration, take appropriate measures to reduce the acceleration or the amplitude.
We recommend the installation of the S7-1500 automation system/ET 200MP distributed I/O
system on damping materials (for example, rubber-bonded metal mounting).
Climatic ambient conditions
The following table shows the permissible climatic ambient conditions for the S7-1500
automation system/ET 200MP distributed I/O system:
Table 16- 8 Climatic ambient conditions
Ambient conditions
Permissible range
Comments
Temperature:
horizontal mounting posi-
tion:
vertical mounting position:
0 °C to 60 °C
0 °C to 40 °C
To increase the service life of the display, the
display switches off when the permitted op-
erating temperature is exceeded.
Further information about the temperatures
at which the display switches off and back on
again is available in the technical specifica-
tions of the manuals of the CPUs.
Temperature variation
10 K/h
-
Relative humidity
from 10 % to 95 %
Without condensation, corresponds to rela-
tive humidity (RH) class 2 in accordance with
IEC 61131 part 2
Barometric pressure
from 1140 to 795 hPa
corresponds to an altitude of -1000 m to
2000 m
Pollutant concentration
ISA-S71.04 severity level G1; G2; G3
-
Summary of Contents for Simatic S7-1500/ET 200MP