Rated voltage for operation
The S7-1500 automation system/ET 200MP distributed I/O system works with the rated
voltages and corresponding tolerances listed in the following table.
Note the supply voltage of each module when selecting the rated voltage.
Table 16- 9 Rated voltage of all modules of the S7-1500 automation system/ET 200MP distributed
I/O system for operation
rated voltage
Tolerance range
24 V DC
19.2 V DC to 28.8 V DC
1
48 V DC
40.8 to 57.6 V DC
60 V DC
51.0 to 72.0 V DC
120 V AC
93 V AC to 132 V AC
230 V AC
187 V AC to 264 V AC
1
Static value: Creation as functional extra-low voltage with safe galvanic isolation according to
IEC 60364-4-41.