Commissioning
11.3 Procedure for commissioning the S7-1500 automation system
Automation system
226
System Manual, 12/2017, A5E03461182-AE
Requirements: CPU as bus device
Note the following requirements for operation of a CPU as bus device:
●
PROFIBUS interface
–
The integrated PROFIBUS interface of the CPU is configured using STEP 7 (device
address and bus parameters configured).
–
The CPU is connected to the subnet.
–
The terminating resistors at the segment boundaries are switched on.
See the PROFIBUS Function Manual
http://support.automation.siemens.com/WW/view/en/59193579
●
PROFINET interface
–
The integrated PROFINET interface of the CPU is configured using STEP 7 (IP
address and device name configured).
–
The CPU is connected to the subnet.
See the PROFINET Function Manual
http://support.automation.siemens.com/WW/view/en/49948856
11.3.1
Removing/inserting a SIMATIC memory card on the CPU
Requirements
The CPU only supports pre-formatted SIMATIC memory cards. If applicable, delete all
previously stored data before using the SIMATIC memory card. Additional information about
deleting the contents of the SIMATIC memory card can be found in the section SIMATIC
memory card - overview (Page 259).
In order to work with the SIMATIC memory card, first ensure that the SIMATIC memory card
is not write-protected. For this purpose, slide the slider on the SIMATIC memory card out of
the lock position.
If the inserted SIMATIC memory card is write-protected, the CPU display outputs the
symbol in the "Memory card" menu under "Overview" and writes a corresponding alarm to
the lower level of the menu.