Application planning
3.3 Configuration versions
S7-1500R/H redundant system
System Manual, 10/2018, A5E41814787-AA
55
3.3.1
S7-1500R/H configuration with IO devices in the PROFINET ring
Introduction
The following sections set out configurations of the S7-1500R/H redundant system with IO
devices in the PROFINET ring.
Advantages/benefits
●
The IO devices are connected in the PROFINET ring with system redundancy.
●
The redundant system continues to operate following a cable interruption anywhere in the
PROFINET ring. One of the two communication connections of the IO devices remains. A
SYNCUP is prevented.
S7-1500R configuration
①
CPU 1
②
CPU 2
③
PROFINET cable (redundancy connections, PROFINET ring)
④
IO device ET 200MP (with system redundancy S2)
⑤
IO device ET 200SP (with system redundancy S2)
Figure 3-2
S7-1500R configuration with IO devices in the PROFINET ring
Summary of Contents for Simatic S7-1500H