Commissioning
9.7 Time synchronization
S7-1500R/H redundant system
240
System Manual, 10/2018, A5E41814787-AA
9.7.1
Example: Configuring the NTP server
Configuring time synchronization with your own NTP server
Automation task
You use your own server in your network. Your own server offers the following advantages:
●
Protection against unauthorized external accesses
●
Every device that you synchronize with your own NTP server uses the same time.
You want to synchronize the CPUs of your S7-1500R/H redundant system with this NTP
server.
Conditions and parameters
●
You have your own NTP server in your network with the IP address 192.168.1.15.
●
S7-1500R/H redundant system
Solution
1.
Navigate to "Properties > General > PROFINET interface > Time synchronization > NTP
mode" in the properties of the first CPU.
2.
For "Server 1:", enter the IP address of the NTP server: 192.168.1.15.
Figure 9-16 Example: Configuring the NTP server
3.
Repeat steps 1 and 2 for the second CPU.
4.
Download the hardware configuration to the primary CPU.
Result
The S7-1500R/H redundant system synchronizes the time with NTP server 192.168.1.15.