General Technical Specifications
National and International Standards
The national and international standards listed below were used to determine appropriate
performance specifications and testing for the S7-200 family of products. Table A-1 defines
the specific adherence to these standards.
S
Underwriters Laboratories, Inc.: UL 508 Listed (Industrial Control Equipment)
S
Canadian Standards Association: CSA C22.2 Number 142 Certified (Process Control
Equipment)
S
Factory Mutual Research: FM Class I, Division 2, Groups A, B, C, & D Hazardous
Locations, T4A
S
VDE 0160: Electronic equipment for use in electrical power installations
S
European Community (CE) Low Voltage Directive 73/23/EEC
EN 61131-2: Programmable controllers - Equipment requirements
S
European Community (CE) EMC Directive 89/336/EEC
Electromagnetic emission standards:
EN 50081-1: residential, commercial, and light industry
EN 50081-2: industrial environment
Electromagnetic immunity standards:
EN 50082-2: industrial environment
Technical Specifications
The S7-200 CPUs and all S7-200 expansion modules conform to the technical specifications
listed in Table A-1.
Table A-1
Technical Specifications for the S7-200 Family
Environmental Conditions — Transport and Storage
IEC 68-2-2, Test Bb, Dry heat &
IEC 68-2-1, Test Ab, Cold
-40
°
C to +70
°
C
IEC 68-2-30, Test Db, Damp heat
25
°
C to 55
°
C, 95% humidity
IEC 68-2-31, Toppling
100 mm, 4 drops, unpacked
IEC 68-2-32, Free fall
1 m, 5 times, packed for shipment
Environmental Conditions — Operating
Functional range
1
0
°
C to 55
°
C, 95% maximum non-condensing humidity
IEC 68-2-14, Test Nb
5
°
C to 55
°
C, 3
°
C/minute
IEC 68-2-27 Mechanical shock
15 G, 11 ms pulse, 6 shocks in each of 3 axis
IEC 68-2-6 Sinusoidal vibration
0.35 mm peak-to-peak 10 to 57 Hz; 2 G panel mount, 1G din rail mount,
57 to 150 Hz; 10 sweeps each axis, 1 octave/minute
EN 60529, IP20 Mechanical protection
Protects against finger contact with high voltage as tested by standard
probes. External protection is required for dust, dirt, water, and foreign
objects of less than 12.5 mm in diameter.
CPU 210 Data Sheets
Summary of Contents for Simatic S7-200 CPU 210
Page 10: ...x S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 Contents ...
Page 116: ...A 16 S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 CPU 210 Data Sheets ...
Page 126: ...F 2 S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 CPU 210 Order Numbers ...
Page 138: ...Index 12 S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 Index ...