Error Handling and Error Codes
Non-Fatal Errors (Compile Rule Violations)
When you download a program, the PDS 210 compiles the program. If the PDS 210 detects
that the program violates a compile rule (such as an illegal instruction), the PDS 210 aborts
the download and generates a non-fatal, compile-rule error code. Table C-1 describes the
error codes that are generated by violations of the compile rules.
Table C-1 Compile Rule Violations
Error Code
Non-Fatal Errors (Compile Rule Violations)
0080
Program too big to compile; you must reduce the program size.
0081
Stack underflow; too many And Load (ALD) or Or Load (OLD) instructions in one
network.
0082
Illegal instruction; check instruction mnemonics.
0083
Missing MEND or instruction not allowed in main program: add a MEND
instruction, or remove incorrect instruction.
0087
Missing Label (LBL or INT); add the appropriate label.
0089
Missing RETI or instruction not allowed in an interrupt routine: add RETI to the end
of the interrupt routine or remove incorrect instruction.
008C
Duplicate Label (LBL or INT); rename one of the labels.
008D
Illegal Label (LBL or INT); ensure the number of labels allowed was not exceeded.
0090
Illegal parameter; verify the allowed parameters for the instruction.
0091
Range error (with address information); check the operand ranges.
0092
Error in the count field of an instruction (with count information); verify the
maximum count size.
Fatal Error Codes and Messages for the PDS 210
You cannot access the error codes for the CPU 210. The information about error codes is
provided to help you identify problems with your PDS 210 program development station.
Fatal errors cause the PDS 210 to stop the execution of your program. Depending on the
severity of the error, a fatal error can render the PDS 210 incapable of performing any or all
functions. The PDS 210 attempts to perform the following tasks when a fatal error is
detected:
S
Changes the mode of operation to the STOP mode
S
Turns on the System Fault LED
S
Turns off the outputs
C
Summary of Contents for Simatic S7-200 CPU 210
Page 10: ...x S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 Contents ...
Page 116: ...A 16 S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 CPU 210 Data Sheets ...
Page 126: ...F 2 S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 CPU 210 Order Numbers ...
Page 138: ...Index 12 S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 Index ...