Maintenance
8.1 Inspection and maintenance
1PH808/1PH810 main motors
134
Operating Instructions, 04/2017, 610.48004.40f
After cleaning
1.
Allow the motor and external cooling unit to dry off.
2.
After wet cleaning, check the insulation resistance.
3.
If used, remove the rotation locks for the fan blades.
4.
Screw the guard (with fan) back onto the cooling unit.
To do so, for 1PH808, tighten 4 screws, and for the 1PH810, 6 screws with a torque of
3.8 Nm ±0.6 Nm.
5.
Check that you have removed all cleaning equipment and cleaning agents.
6.
Check that you have re-attached any parts that were removed for cleaning.
7.
Reconnect the power supply.
8.
Switch on the motor and external cooling unit again.
8.1.8
Replacing an encoder
When replacing the motor bearings, we also recommend that you replace the encoder
equipped with their own bearings.