Diagnostics
11.2 List of faults and alarms
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
387
11.2
List of faults and alarms
This section lists only common faults and alarms. To view the detailed information of all
faults and alarms, call the online help for an active fault/alarm in the SINAMICS V-
ASSISTANT engineering tool.
Fault list
Fault
Cause
Remedy
F1000: Internal software error
Reaction: OFF2
Acknowledgement: POWER
ON
An internal software error has occurred.
•
Evaluate fault buffer.
•
Carry out a POWER ON (power off/on) for
all components.
•
Upgrade firmware to later version.
•
Contact the Hotline.
•
Replace the Control Unit.
F1001: FloatingPoint excep-
tion
Reaction: OFF2
Acknowledgement: POWER
ON
An exception occurred during an operation
with the FloatingPoint data type.
•
Carry out a POWER ON (power off/on) for
all components.
•
Upgrade firmware to the latest version.
•
Contact the Hotline.
F1002: Internal software error
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
An internal software error has occurred.
•
Carry out a POWER ON (power off/on) for
all components.
•
Upgrade firmware to the latest version.
•
Contact the Hotline.
F1003: Acknowledgement
delay when accessing the
memory
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
A memory area was accessed that does
not return a "READY".
•
Carry out a POWER ON (power off/on).
•
Contact the Hotline.
F1015: Internal software error
Reaction: OFF2
Acknowledgement: POWER
ON
An internal software error has occurred.
•
Carry out a POWER ON (power off/on) for
all components.
•
Upgrade firmware to the latest version.
•
Contact the Hotline.