Networking
7-106
E
Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
7.2
Network components for PROFIBUS subnet
Overview
This section contains information on:
S
PROFIBUS bus cable
S
Bus connector
S
Plugging the bus connector into the module
7.2.1
PROFIBUS bus cable
We can supply you with the following PROFIBUS bus cables:
Cable
Order No.
PROFIBUS bus line
6XV1 830-0AH10
PROFIBUS grounding cable
6XV1 830-3AH10
PROFIBUS trailing cable
6XV1 830-3BH10
Characteristics of the PROFIBUS bus cable
The PROFIBUS bus cable is a two-core, twisted and shielded cable with the fol-
lowing characteristics:
Table 7-2
Characteristics of the PROFIBUS bus cable
Features
Values
Surge resistance
approx. 135 to160
Ω
(f
=
3 to 20 MHz)
Loop resistance
x
115
Ω
/km
Operating capacity
30 nF/km
Attenuation
0.9 dB/100 m (f = 200 kHz)
Permissible core cross-section
0.3 mm
2
to 0.5 mm
2
Permissible cable diameter
8 mm
"
0.5 mm