Device Data
3-40
E
Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
Connecting cable to the encoder
The maximum cable length depends on the specification for the encoder supply
and the baud rate. If you use pre-assembled SIEMENS connecting cables (see
Catalogs NC Z/NC 60/ST 70), problem-free operation can be guaranteed only if
the following values are not exceeded:
Table 3-9
Maximum cable lengths, depending on the encoder power supply
Supply voltage
Encoder supply
voltage range
Power con-
sumption
Max. cable length
5 VDC
4.75 V...5.25 V
< 300 mA
25 m
5 VDC
4.75 V...5.25 V
< 210 mA
35 m
24 VDC
20.4 V...28.8 V
< 300 mA
100 m
24 VDC
11 V...30 V
< 300 mA
250 m
Table 3-10
Maximum cable lengths, depending on the baud rate
Encoder type
Frequency
Max. cable length
1 MHz
10 m
Incremental encoder
500 kHz
35 m
1.5 Mbits/s
10 m
Absolute encoder (SSI)
187.5 Kbyte/s
250 m