Device Data
3-54
E
Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
Digital outputs (according to IEC 1131-2/DIN EN 61131-2)
Number of outputs
8
Supply voltage
24 VDC (permissible range: V
L
= 20.4...28.8 V)
Output voltage
1-signal: From V
L
1)
– 0.8 V to V
L
1)
V
Max. output current
1-signal: 5 mA...0.6 A (via supply voltage)
Aggregate current of outputs
S
Max. 4 A (at 0... 40
°
C )
S
Max. 2 A (at 40...55
°
C)
Extinguishing energy per output
400 mJ (not simultaneous)
Lamp load
5 W
Switching frequency
S
100 Hz (with resistive load)
S
2 Hz (with inductive load)
Short-circuit protection
Max. leakage current
Yes
0-signal: 2 mA
Output delay (Q0...Q7)
S
0
→
1-signal: 500
µ
s (type 150
µ
s) at RL = 60 Ohm
S
1
→
0-signal: 500
µ
s (type 150
µ
s) at RL = 60 Ohm
Electrical isolation between out-
puts
Electrical isolation between out-
puts and logic
Isolation
No
Yes
500 V
1) V
L
– Supply voltage of outputs
Note
The connection cable between the voltage source and the load current supply con-
nector L+ and the associated reference potential M should not exceed a maximum
length of 10 m.
READY output (RDY)
Table 3-15 Electrical parameters of RDY contact assembly
Contact assembly RDY
Switching voltage DC
Max. 50 V
Switching current
Max. 1 A
Switching capacity
Max. 30 VA
Mechanical service life
Electrical service life
Usually 10
9
switching cycles
Usually 3*10
6
switching cycles at 24 V/1 A
Summary of Contents for SIMOTION C230-2
Page 16: ...Product Overview 1 16 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Page 70: ...Installation 4 70 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Page 124: ...Commissioning 8 124 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Page 130: ...Maintenance 9 130 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...