Installation
4-58
E
Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
4.1
Design and configuration using SIMOTION C modules
Overview
This chapter contains information on:
S
Horizontal and vertical configuration
S
Clearances
S
Mounting dimensions of modules
S
Layout of modules on a rack
S
Layout of modules on several racks
4.1.1
Horizontal and vertical configuration
Configuration
You can install the rack either horizontally or vertically. The horizontal configuration
should be used if possible.
Permissible ambient temperature
S
Horizontal configuration: From 0 to 55
_
C
S
Vertical configuration:
From 0 to 40
_
C
Horizontal configuration
Vertical configuration
C230-2 and the power supply are
always to be placed on the left or bottom.
Fig. 4-1
Horizontal and vertical configuration