Connection
7
7.1
Requirements
General information
During the configuration of SIMOTION modules, you must pay attention to the "Electrical
configuration design".
The following section provides information on wiring and networking the complete SIMOTION
system.
Further information about the connection of the complete system and the individual
components can be found in the SIMOTION P320-4 E / P320-4 S Commissioning and
Hardware Installation Manual
.
Open equipment
These modules are open equipment. This means they may only be installed in housings,
cabinets, or in electrical equipment rooms that can only be entered or accessed with a key or
tool. Housings, cabinets, or electrical equipment rooms may only be accessed by trained or
authorized personnel. An external fire-protection housing is required.
Observe the following points during installation:
● The device should be connected only to 24 VDC power supply networks that meet the
requirements of safety extra-low voltage (SELV). The cable cross-section must be chosen
large enough to ensure that no damage can result from cable overheating in the event of
a short-circuit in the SIMOTION P320-4.
● Avoid extreme ambient conditions.
● Protect the device against dust, moisture, heat and severe vibration.
● Do not subject the SIMOTION P320-4 to direct sunlight.
● Install the device in such a way that it poses no danger, for example, by falling over.
● The clearance around the SIMOTION P320-4 must be at least 100 mm to ensure adequate
ventilation.
● Do not cover the ventilation slots.
SIMOTION P320-4 E / P320-4 S
Manual, 03/2018, A5E36004933B
113