Field/Button
Significance/Note
Axis modulo length
(See the Relation of
track length, modulo
length, and activation
mode section)
The modulo length of the axis, which the cam track is linked to, is displayed here. The modulo length
does not have to be identical to the track length. To change the modulo length of the axis, you must
work through the axis wizard.
It is only displayed when the axis is configured as a modulo axis.
Activation time
(See the Actuation
times (activation time/
deactivation time)
section)
Enter the activation time here. The output cam switching time is set to the point when the start position
is reached, plus this period. The output cam position is adapted dynamically. This allows you to
compensate for propagation delays.
If a negative value is entered as an activation time, the switching signal is activated before the start
position is reached.
Deactivation time
Enter the deactivation time here. The output cam switch-off time is set to the point when the end
position is reached, plus this period. The output cam position is adapted dynamically. This allows
you to compensate for propagation delays.
If a negative value is entered as a deactivation time, the switching signal is activated before the end
position is reached.
Hysteresis
(See the Hysteresis
section)
Enter a range for the hysteresis here. The output cam does not change its switching state in this
defined range around the switching position even under changed switching conditions. This prevents
a repeated change of the switching state.