03.99
Communication via CC-Link
Siemens AG
6SE7087-6NX84-0GB0
SIMOVERT MASTERDRIVES
Operating Instructions
4-3
Device No
Signal name
Description
RXn0
Forward operation
OFF: Other than forward operation
ON: Forward operation
RXn1
Reverse operation
OFF: Other than reverse operation
ON: Reverse operation
RXn2
Running (RUN)
ON during the inverter operation
RXn3
Frequency reached (SU)
ON when output frequency is in the set frequency
±
permission
deviation; refer to function diagram 480 and status word bit 8
RXn4
Overload (OL)
ON when inverter overload warning is active; refer to status
word bit 22
RXn5
Momentary power failure
(IPF)
ON when momentary power failure occurs; refer to status word
bit 11 "Low voltage fault"
RXn6
Frequency detection (FU)
ON when comparison value is reached; refer to function
diagram 480 and status word bit 10
RXn7
Abnormal (ABC)
ON when inverter protection function is activated and the output
stopped.
RXn8
Info flag 0 (I0)
Additional info flag: Status word bit 0 "Ready to switch on"
Refer to chapter 4.11 "Optional flags in CBL profile"
RXn9
Info flag 7 (I7)
Additional info flag: Status word bit 7 "Warning active"
Refer to chapter 4.11 "Optional flags in CBL profile"
RXnA
Info flag 15 (I15)
Additional info flag: Status word bit 15
Refer to chapter 4.11 "Optional flags in CBL profile"
RXnC
Monitoring
ON when the monitor value is set in RWrm while the monitor
command (RYnC) is ON. It turns OFF when the monitor
command (RYnC) is turned OFF.
Refer to chapter 4.5 "Monitoring"
RXnD
Frequency setting
complete (RAM)
ON when frequency is written to the inverter while frequency
set command (RYnD) is ON. It turns OFF when the frequency
set command (RYnD) is turned OFF.
Refer to chapter 4.4 "Setpoint handling"
RXnF
Command code execution
complete
ON when process corresponding to command code (RWwm+2)
is executed and completed by turning ON the command code
execution request (RYnF). It turns OFF when the command
code execution request (RYnF) is turned OFF.
Refer to chapter 4.6 "Command code execution"
RX (n+1)8
Initial data processing
request flag
After power-on or new initializing the initial data processing
request flag is turned on by CBL.
Refer to chapter 4.3 "Initial process and initial data setting"
RX (n+1)9
Initial data setting
complete flag
When the initial data setting request (RY(n+1)9 is ON) is
issued, it turns ON after initial data setting is completed.
Refer to chapter 4.3 "Initial process and initial data setting"
RX (n+1)A
Error status flag
ON when the inverter has an error.
Refer to chapter 4.3 "Initial process and initial data setting"
RX (n+1)B
Remote ready
ON after initial process or initial data setting. OFF during error
status is ON;
Refer to chapter 4.3 "Initial process and initial data setting"
Table 4-2
CC-Link Profile CBL: Bit definition
All manuals and user guides at all-guides.com
Summary of Contents for Simovert Masterdrive FANC-SB
Page 8: ...All manuals and user guides at all guides com ...
Page 14: ...All manuals and user guides at all guides com ...
Page 48: ...All manuals and user guides at all guides com ...
Page 58: ...All manuals and user guides at all guides com ...
Page 70: ...All manuals and user guides at all guides com ...
Page 72: ...All manuals and user guides at all guides com ...