03.99
Start-up of the CBL
Siemens AG
6SE7087-6NX84-0GB0
SIMOVERT MASTERDRIVES
Operating Instructions
5-1
5
Start-up of the CBL
If two communication boards are used the CB in the lower letter slot is
the first one. The CB in the higher letter slot is the second one.
The CB parameters of the first communication board are reached with
index 1, the second with index 2; e.g. P711.2 is parameter P711 of the
second communication board.
At chapter "softwiring" transmit and receive channel have to be routed
to the setpoint and actual value channels. The connectors of the first
CB have numbers like 3XXX, the second CB like 8XXX.
If two CBs are used refer to the documentation and function diagrams
of the converter and check the connector numbers.
5.1
Basic parameterization of the units
Optional boards?
CBL? Yes:
P060 = 4
Function selection "hardware configuration"
CB-Parameter for CBL:
P711 = 0...4
P712 = 0...255
P715 = typ. 350
P716 = typ. 351
P717 = typ. 352
P718 = typ. 353
P918 = 1...64
Data transmission rate
Option switch
Scaling parameter A
Scaling parameter V
Scaling parameter Hz
Scaling parameter rotation/min
CC-Link station number
P060 = 1
Function selection "leave hardware configuration"
P722 = 0...65535
Telegram failure time
P053 = x
Parameterization enable CBL
Go on with
softwiring
See next chapter
Fig. 5-1
Parameterization of the "hardware configuration" for MASTERDRIVES
with CUMC or CUVC
Using two
communication
boards
Basic
parameterization for
MASTERDRIVES with
CUMC or CUVC
All manuals and user guides at all-guides.com
Summary of Contents for Simovert Masterdrive FANC-SB
Page 8: ...All manuals and user guides at all guides com ...
Page 14: ...All manuals and user guides at all guides com ...
Page 48: ...All manuals and user guides at all guides com ...
Page 58: ...All manuals and user guides at all guides com ...
Page 70: ...All manuals and user guides at all guides com ...
Page 72: ...All manuals and user guides at all guides com ...