SIMOLINK Pulse Generator
02.2001
Start-Up
Siemens AG
GWE-477 764 4070.76 J
SIMOVERT MASTERDRIVES
Operating Instructions
6-3
6.3
SIMOLINK data interface
The SIMOLINK data interface comprises a single-channel SIMOLINK
receive data word; it does not provide a transmit channel. It expects the
speed setpoint for the frequency generator in receive channel 0 of the
set receive address. The setpoint is read in the MASTERDRIVES 32-bit
format (4000 0000 hex = 100 %); only the 10 highest bits are resolved,
corresponding to a speed resolution of 0.4 %.
32-bit setpoint from SIMOLINK receive telegram
31
22
16 15
0
Evaluated by the SLP
Irrelevant
Fig. 6-3
SLP setpoint telegram
The frequency generator has a frequency range of 0 Hz to 112 kHz (at
a rated frequency of 100 kHz). In the 90° pulses mode (4 edges
required for correct signal sequence from tracks A and B), the resulting
rated output frequency per track is 25 kHz and a maximum possible
setpoint output of approximately 112 %.
32-bit setpoint
(hex)
Setpoint
[%]
Output frequency in
90°pulses mode [kHz]
Frequency in
100 kHz / sign mode
47C0 0000
+ 112.1
28.027
112.1 kHz / Low
4780 0000
+ 111.7
27.930
111.7 kHz / Low
4000 0000
+ 100.0
25.000
100.0 kHz / Low
0000 0000
0.0
0.000
0.0 kHz / Low
C000 0000
−
100.0
25.000
100.0 kHz / High
B880 0000
−
111.7
27.930
111.7 kHz / High
B840 0000
−
112.1
28.027
112.1 kHz / High
Table 6-3
Relationship between setpoint and output frequency
When the setpoint exceeds 112 %, the SIMOLINK Pulse Generator
outputs the maximum frequency of approximately 28 kHz. If "100 kHz
signal“ mode is active, then approximately 112 kHz.