Version 1.0 March 1, 2000
Page 19
P453 = -100
P060 = 1
P128 = xxxx
P462 = xxxx
P464 = xxxx
P443i2= 11
P453 = Maximum Reverse Speed in
Percentage (usually -100%)
P060 = Return to Parameter Menu
P128 = Maximum Motor Current
Options:
P128 = P102
P128=1.1*P102
P128=1.5*P102
P462 = Acceleration Time in seconds
P464 = Deceleration Time in seconds
P443i2(Index2) = 11
Configures drive for analog input
(0-10Vdc) to be active at
terminals X101 pin#15 and
pin#16
If 4-20mA is required closed
CUVC board mounted jumper
S3, position 1 and 2.
Start/Stop Control is located on
the PMU (operator control panel
mounted directly on the drive)
Speed Setpoint is controlled with
the Up / Down arrows.