Additional Connection for +15 Vdc Encoder.
Step 10: Set Speed Reference to 20%.
Step 11: Provide Start command. Note that if Signal A and Signal B are
reversed, the motor will accelerate rapidly.
Step 12: Connect the motor to the load, unless the plan is to change to
Vector Control.
Standard Commissioning for a Volts/Hz
controlled motor with feedback is
complete, after adjusting only 24
parameters.
Summary of Contents for SIMOVERT MASTERDRIVES 6SE70 VC