Function diagram
8
7
6
5
4
3
2
1
fp_mc_491_e.vsd
Protective functions
MASTERDRIVES MC
18.01.06
Part 2
- 491 -
V2.5
to status word 2, bit 25 [210.2]
A023:
Motor overtemperature
to status word 2, bit 26 [210.2]
F020:
Motor overtemperature fault
Encoder evaluation, slot C
0
1
1
0
from evaluation of
actual-values
[500.8]
1
0
A029:
Alarm motor overtemperature
to status word 2, bit 25 [210.2]
F021:
Fault motor overtemperature
to status word 2, bit 26 [210.2]
i2t Calculation
Motor temperature monitoring:
No temperature sensor:
P131 = 0
Monitoring with KTY84:
P131 = 1
PTC monitoring:
P131 = 2
Monitoring with PT100:
P131 = 3
Monitoring with KTY83:
P131 = 4
Coupling via Src Motor Temp.:
P131 = 5
Temperature
evaluation
It is not possible to evaluate the motor temperature for
encoder evaluations that are not inserted in slot C.
WARNING
0
1
1
0
2 °C
0
1
F020:
Motor overtemperature fault
max. temp = 140 °C
min. temp = -55 °C
X
3
KTY83 selected
X
5
Mot Tmp Fault
0 ... 300 °C
P381 (120)
Mot Tmp Warning
0 ... 300 °C
P380 (100)
Motor Temperat.
r009
K0245
Motor Temperat.
Select TmpSensor
0 ... 5
P131 (1)
n959.63 = P357
K0242
OutputAmps(rms)
Motor Utilization
r008
Mot. Load Limits
0 ... 300 %
P384.1 (100 %)
0
Mot. Load Limits
0 ... 300 %
P384.2 (100 %)
K
P138
Q.MotorTemp
Motor Cooling
0 ... 1
P382 (1)
Mot.Temp.T1
0 ... 16 000 s
P383 (100 s)
0) Otherwise
1) For
●
no temperature sensor (P131 = 0)
and
●
P383
≥
100 s