Parameter
Description
Data
Read/write
P098*
Torque constant
98
Torque constant at standstill and maximum motor
temperature (140 ºC ) M0 / I0. Designation [Nm/A].
The value is slightly higher than the rated torque / rated
current because there are no friction and iron losses at
standstill. When the kT-estimator is activated, an
estimated value for this torque constant can be read in
parameter r88.
Please keep in mind that the value range is restricted to
0.8 * (M_rated/I_rated) <= P098 <= 1.5 *
(M_rated/I_rated). Therefore, the values for the motor
rated current P102 and the motor rated torque P113 must
already have been entered before you make any changes
to P098.
Init: 1,40
Min: 0,10
Max: 655,00
Unit: Nm/A
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P099*
Select 1FW3
99
Function parameter for selecting torque motor 1FW3 from
the internal motor list.
See Compendium appendix for parameter values.
Init: 0
Min: 0
Max: 253
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Quick parameterization
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P101*
Mot Rtd Volts
101
Function parameter for entering the rated motor voltage
for a connected induction motor. The rating-plate value is
to be entered for the current type of connection (star or
delta).
Init: 400
Min: 100
Max: 1000
Unit: V
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P102*
Motor Rtd Amps
102
Function parameter for entering the rated motor current of
the connected synchronous or induction motor. The rating-
plate value is to be entered for the current type of
connection (star or delta).
Init: 0,00
Min: 0,00
Max: 1300,00
Unit: A
Indices: -
Type: I4
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P103*
Mot No Load Amps
103
Function parameter for entering the motor no-load current
for the connected induction/synchronous motor.
For the connected induction motor a motor no-load
current smaller than the rated motor current (P102) is to
be entered.
For the connected synchronous motor the motor no-load
current value 0 A is to be entered.
Init: 0,00
Min: 0,00
Max: 1300,00
Unit: A
Indices: -
Type: O4
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
P104*
MotPwrFactor
104
Function parameter for entering the power factor for the
connected induction motor. The rating-plate value is to be
entered.
Init: 0,800
Min: 0,500
Max: 0,999
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Motor/encoder
+ Motor data
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
12
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control