Parameter
Description
Data
Read/write
P588*
S.No Ext Warn1
588
BICO parameter for selecting the binector from which the
command for tripping an external warning 1 (control word
2, bit 28) is to be read in.
index1: 1
Unit: -
Indices: 2
,BDS
Type: L2 ,B
Menus:
- Parameter menu
+ Control and status
words
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P589*
S.No Ext Warn2
589
BICO parameter for selecting the binector from which the
command for tripping an external warning 2 (control word
2, bit 29) is to be read in.
index1: 1
Unit: -
Indices: 2
,BDS
Type: L2 ,B
Menus:
- Parameter menu
+ Control and status
words
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P590*
S.BICO DSet
590
BICO parameter for selecting the binector from which the
bit for selecting a BICO data set (control word 2, bit 30) is
to be read in.
Init: 0
Unit: -
Indices: -
Type: L2 ,B
Menus:
- Parameter menu
+ Control and status
words
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P591*
S.ContactorMsg
591
BICO parameter for selecting the binector from which the
check-back message of a main contactor (control word 2,
bit 31) is to be read in. If a source for the check-back
message of the main contactor is not parameterized
(input value = 0), the check-back time parameterized in
P600 is waited out after the ON command and then
precharging is started. If a source for the check-back
message of the main contactor is parameterized (input
value not equal to 0), a transition to precharging only
takes place when the check-back message is logical 1.
index1: 0
Unit: -
Indices: 2
,BDS
Type: L2 ,B
Menus:
- Parameter menu
+ Control and status
words
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P595*
Cl/AntiClRot
595
The parameter defines the direction of rotation of the
motor.
P595=0: At positive setpoint setting, the drive rotates to
the right.
P595=1: At positive setpoint setting, the drive rotates to
the left.
The following quantities are influenced:
a) Speed actual value
b) Current setpoint
c) Position actual value
d) Absolute value of multiturn encoder
The practical application lies, for example, in continuous
webs, so that all drives rotate in the direction of the
material with positive setpoint setting.
In the case of positioning tasks, the direction of motion
and the zero position can be defined irrespective of the
motor's direction of rotation.
It is possible to imagine the function as follows: two
phases are reversed on the drive (change in the rotating-
field direction) and the speed actual value is inverted
(restoring the sense of control)
It must be noted that the pulse encoder simulation of SBM
and SBR2 show the real shaft speed. The parameter has
no influence on these signals.
In function diagram 500a.4
Init: 0
Min: 0
Max: 1
Unit: -
Indices: -
Type: O2
Menus:
- Parameter menu
+ Setpoint channel
- Drive setting
- Upread/free access
Changeable in:
- Drive setting
74
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control