Parameter
Description
Data
Read/write
P664*
EB1 AnaOut Conf
664
Parameter for configuring the analog outputs on EB1.
Selection of the sign is made here with which the value of
the connector selected in P663 has to be output at the
analog output.
0 = Do not change sign
1 = Always output value with positive sign
2 = Invert sign
3 = Always output value with negative sign
Index 1 and 2: AO1 and AO2 of the first inserted EB1
Index 3 and 4: AO1 and AO2 of the second inserted EB1
index1: 0
Min: 0
Max: 3
Unit: -
Indices: 4
Type: O2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P665*
EB1 AnaOutSmooth
665
Parameter for entering the smoothing time constants for
the analog outputs on EB1.
Index 1 and 2: AO1 and AO2 of the first inserted EB1
Index 3 and 4: AO1 and AO2 of the second inserted EB1
index1: 0
Min: 0
Max: 10000
Unit: -
Indices: 4
Type: O2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P666*
EB1AnaOutNorm
666
Parameter for scaling the analog outputs on EB1. With
the help of the entered parameter value, the analog output
voltage to which an internal signal value of 100% (4000 H)
should correspond is determined.
Index 1 and 2: AO1 and AO2 of the first inserted EB1
Index 3 and 4: AO1 and AO2 of the second inserted EB1
index1: 10,00
Min: -200,00
Max: 200,00
Unit: V
Indices: 4
Type: I2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P667
EB1 AnaOutOffset
667
Parameter for entering the offset for the analog outputs on
EB1. The offset is added to the already scaled analog
output signal.
Index 1 and 2: AO1 and AO2 of the first inserted EB1
Index 3 and 4: AO1 and AO2 of the second inserted EB1
index1: 0,00
Min: -200,00
Max: 200,00
Unit: V
Indices: 4
Type: I2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
r668
EB1 AnaOut Value
668
Visualization parameter for displaying the actual values
which are connected to the analog outputs of EB1.
Index 1 and 2: AO1 and AO2 of the first inserted EB1
Index 3 and 4: AO1 and AO2 of the second inserted EB1
Dec.Plc.: 2
Unit: %
Indices: 4
Type: I2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
P669*
EB1 S.DigOut
669
Parameter for selecting the binectors whose values have
to be output at terminal -X480/43 to 46 of EB1. The
relevant index of the binector has to be set to 0 in order to
use terminal -X480/43 to 48 as digital inputs.
Index 1 to 4: DO1 to DO4 of the first inserted EB1
Index 5 to 8: DO1 to DO4 of the second inserted EB1
index1: 0
Unit: -
Indices: 8
Type: L2 ,B
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
r670
EB1 TerminalDisp
670
Visualization parameter for displaying the signal level of
the digital inputs and outputs of EB1.
Index 1: First inserted EB1
Index 2: Second inserted EB1
Dec.Plc.: 0
Unit: -
Indices: 2
Type: V2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
r673
EB2 Termin Disp
673
Visualization parameter for displaying the signal level of
the digital inputs and outputs of EB2
Index 1: First inserted EB2
Index 2: Second inserted EB2
Dec.Plc.: 0
Unit: -
Indices: 2
Type: V2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
P674*
EB2 S.RelayOut
674
Parameter for selecting the binectors for activation of the
relay outputs on EB2.
Index 1 to 4: Relay outputs of the first inserted EB2
Index 5 to 8: Relay outputs of the second inserted EB2
index1: 0
Unit: -
Indices: 8
Type: L2 ,B
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
82
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control