Parameter
Description
Data
Read/write
P675*
EB2 Signal Type
675
Parameter for selecting the signal type for the analog
input on EB2.
0 = +/- 10 V
1 = +/- 20 mA
Index 1: First inserted EB2
Index 2: Second inserted EB2
index1: 0
Min: 0
Max: 1
Unit: -
Indices: 2
Type: O2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
P676*
EB2 AnaInNorm
676
Parameter for normalizing the analog input on EB2.
Incoming signals are multiplied by the entered parameter
value.
Index 1: First inserted EB2
Index 2: Second inserted EB2
index1: 1,00
Min: 0,00
Max: 100,00
Unit: -
Indices: 2
Type: O2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P677
EB2 AnaInOffset
677
Parameter for entering the offset for the analog input on
EB2. The offset is added to the already scaled analog
input signal.
Index 1: First inserted EB2
Index 2: Second inserted EB2
index1: 0,00
Min: -100,00
Max: 100,00
Unit: -
Indices: 2
Type: I2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
P678*
EB2 AnaInConf
678
Function parameter for configuring the analog input on
EB2. Selection is made here of the sign with which the
read-in analog value has to be provided.
0 = Do not change sign
1 = Always pass on value with positive sign
2 = Invert sign
3 = Always pass on value with negative sign
Index 1: First inserted EB2
Index 2: Second inserted EB2
The sign can be changed again by the "Invert analog
input" command (P681).
index1: 0
Min: 0
Max: 3
Unit: -
Indices: 2
Type: O2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
P679*
EB2 S.AnaInInv
679
Parameter for selecting the binector from which the
command to invert the analog input signal on EB2 has to
be read in.
Index 1: First inserted EB2
Index 2: Second inserted EB2
index1: 0
Unit: -
Indices: 2
Type: L2 ,B
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P680*
EB2 AnaInSmooth2
680
Parameter for entering the smoothing time constant for
the analog input on EB2.
Index 1: First inserted EB2
Index 2: Second inserted EB2
index1: 0
Min: 0
Max: 1000
Unit: ms
Indices: 2
Type: O2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
P681*
EB2 S.AnaInRel
681
Parameter for selecting the binector from which the
command to enable the analog input on EB2 has to be
read in. Without an enable, the setpoint provided by the
analog input is at 0.
Index 1: First inserted EB2
Index 2: Second inserted EB2
index1: 1
Unit: -
Indices: 2
Type: L2 ,B
Menus:
- Parameter menu
+ Terminals
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
r682
EB2 AnaIn Setp
682
Visualization parameter for displaying the setpoint which
is provided by the analog input of EB2.
Index 1: First inserted EB2
Index 2: Second inserted EB2
Dec.Plc.: 2
Unit: %
Indices: 2
Type: I2
Menus:
- Parameter menu
+ Terminals
- Upread/free access
83
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control