Parameter
Description
Data
Read/write
U608*
CouplePosition
2608
If the master setpoint exceeds the clutch position, the
engaging/disengaging cycle is started, prior to which the
enable signal must be given.
Function diagram [834.3]
Init: 0
Min: -
2147483648
Max:
2147483647
Unit: -
Indices: -
Type: I4
Menus:
- Parameter menu
+ Technology
+ Synchronism
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U609*
S.OffsetClutchP
2609
Index 1:
Selection of the offset value for the engaging position
during engaging/disengaging action. This value is added
to the engaging position in parameter U608.
Index 2:
Selection of the disengaging position. Only effective if
configuration of engaging/disengaging U475 = 1 or 11.
Parameter U608 has no influence on the disengaging
position
Function diagram [834a.2]
index1: 822
Unit: -
Indices: 2
Type: L2 ,K
,K
Menus:
- Parameter menu
+ Technology
+ Synchronism
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U610*
OnOff Ramp
2610
Index 1:
The parameter determines the number of LU increments
in which the engaging/disengaging action accelerates to
master speed.
Index 2:
The parameter determines the number of LU increments
for the length of a ramp. This ramp can be freely wired via
KK0895.
Example: engaging (U475=0)
----------------------------
Ramp = 10000 LU increments
Engaging length = 100000 LU increments
==> After the start of engaging action, the drive
accelerates in (ramp/2) =5000 inc. up to the master
speed, travels synchronously along the (engaging length
ramp) = (100000-10000) = 90000 inc. with the master
setpoint and is then shut down in 5000 increments.
Function diagram [834a.4]
Example: engaging (U475=11)
-----------------------------
Acceleration ramp = U610.1:
Interconnection of KK0894 to U474.1 results in =>
Src.variable acceleration ramp in LU increments referred
to master
Deceleration ramp
= U610.2:
Interconnection of KK0895 to U474.2 results in =>
Src.variable deceleration ramp in LU increments referred
to master
Function diagram [834b.4]8
index1: 1
Min: 0
Max:
2147483647
Unit: -
Indices: 2
Type: I4
Menus:
- Parameter menu
+ Technology
+ Synchronism
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
U611*
OnOff Length
2611
The parameter determines the number of increments for
the master setpoint which are to be engaged/disengaged
in total. Example see U610.
Function diagram [834a.5] or [834b.5]
Init: 0
Min: 0
Max:
2147483647
Unit: -
Indices: -
Type: I4
Menus:
- Parameter menu
+ Technology
+ Synchronism
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
201
Siemens AG 6SE7087-6QX70 (Edition AL)
SIMOVERT MASTERDRIVES Compendium Motion Control