Parameterizing Steps
08.2012
6SE7087-6QX70 (Version AN) Siemens AG
6-10
Compendium Motion Control
SIMOVERT MASTERDRIVES
Order number
In [A]
PWE
6SE7035-1EK70 -1AA0
or -1AA1
510
1)
423
2) 3)
233
6SE7036-0EK70 -1AA0
or -1AA1
590
1)
491
2) 3)
237
6SE7037-0EK70 -1AA0
oder -1AA1
690.0
4)
168
Order number
In [A]
PWE
6SE7035-1TJ70 -1AA1
or -1AA0
510.0
1)
423
2) 3)
206
6SE7036-0TJ70 -1AA1
or -1AA0
590.0
1)
491
2) 3)
209
6SE7037-0TJ70 -1AA0
or -1AA1
690.0
4)
167
6SE7041-3TL70 -1AA0
or -1AA1
1300.0
4)
199
6SE7038-6TK70 -1AA0
or -1AA1
860.0
4)
213
6SE7041-1TK70 -1AA0
or -1AA1
1100.0
4)
221
1)
theoretical rated output current at 3 kHz pulse frequency; rated output
current can only be achieved if the Power Extension PIN is entered.
2)
rated output current at 5 kHz pulse frequency; the permissible rated output
current will be reduced further at higher pulse frequencies (see technical
data, derating)
3)
This device is a chassis unit (from type J). The overload over 30 s is
therefore limited to 1.36 x the rated output current at 5 kHz.
4)
This unit is a so-called chassis unit and can only be operated up to a
maximum pulse frequency of 2.7 kHz. The overload for 30 s is limited to
1.36 times the rated output current.
Water-cooled AC-AC
frequency converter
Water-cooled DC-AC
inverter