7
Commissioning
SIMPRO-100
110
PRIM-2400C
Table 7.13
Power Measuring Accuracy Test Values, Delta Voltages
Applied Currents
and Voltages
Real Power
(kW)
Reactive Power
(kVar)
Power Factor
(pf)
PHROT = ABC
Expected:
P = 0.4677 • CTR • PTR
Expected:
Q = 0.2286 • CTR • PTR
Expected:
pf = 0.90 lag
Ia = 2.5 A
∠
-26°
Ib = 2.5 A
∠
-146°
Ic = 2.5 A
∠
94°
Vab = 120 V
∠
30°
Measured:
Measured:
Measured:
Vcb = 120 V
∠
90°
PHROT = ACB
Expected:
P = 0.4677 • CTR • PTR
Expected:
Q = 0.2286 • CTR • PTR
Expected:
pf = 0.90 lag
Ia = 2.5 A
∠
-26°
Ib = 2.5 A
∠
94°
Ic = 2.5 A
∠
-146°
Vab = 120 V
∠
-30°
Measured:
Measured:
Measured:
Vcb = 120 V
∠
-90°