Event Analysis
SIMPRO-100
120
PRIM-2400C
– Reactive Power Element Alarm
– Power Factor Element Alarm
– Dropout of any Over- or Underfrequency
Element
If your application requires different performance,
you can change these settings by following the
steps described in Appendix B, page 137.
9.5.2
Retrieving Event Reports
Use the serial port EVENT command to retrieve
event reports. There are several options for
customizing the report format. The general
command format is shown in Table 9.2. Table 9.3
lists example EVE commands.
Table 9.2
Event Commands
Table 9.3
EVE Command Options
The SIMPRO-100 Relay also provides a facility to
allow you to download event report data using
Modbus, protocol and the rear-panel serial port.
For more information, see Appendix C, page 159.
9.5.3
Event Report Data Column
Definitions
The event report data is arranged in columns and
rows. Each column includes a single type of data
such as A-phase current samples or the state of
two output contacts. Each row displays the
measurements and results of a single instant in
time. Event reports you view using the EVENT
command contain four samples per power
system cycle. Raw event reports and the
compressed event format that the SIMPRO-PC
software uses to display oscillographic
information include data for 16 samples per
power system cycle. In event reports, time runs
down the page; first occurrences are shown at
the top of the page, final conditions at the bottom.
Events contain 3 cycles of pretrigger data and 12
cycles of posttrigger data to show the motor and
system conditions before, during, and after the
fault. Definitions and descriptions of the event
report data columns are shown in Table 9.4 and
Table 9.5.
9.5.3.1
Current & Voltage Columns
Table 9.4 summarizes the event report current
and voltage columns
Table 9.4
Event Report Current and Voltage
Columns
Event n R
Where:
n
Event number (1 – 14). Defaults to 1 if not listed,
where 1 is the most recent event. If you request an
event that does not exist, the relay responds
Invalid
Event
.
R
Specifies the unfiltered (raw) event report. Displays 16
samples per cycle.
Serial Port
Command
Description
EVE
Display the most recent event report at
1/4-cycle resolution.
EVE 2
Display the second event report at 1/4-cycle
resolution.
EVE R
Display most recent report at 1/16-cycle
resolution; analog data are not digitally
filtered (raw).
Column
Heading
Definition
IA
Current measured by channel IA (primary A)
IB
Current measured by channel IB (primary A)
IC
Current measured by channel IC (primary A)
IG
Residual current (IA + IB + IC, primary A)
IN
Current measured by channel IN (primary A)
VA or VAB Voltage measured by channel VA or VAB
(primary V)
VB or VBC Voltage measured by channel VB or VBC
(primary V)
VC or VCA Voltage measured by channel VC or
calculated from VAB and VBC (primary V)
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......