![background image](http://html.mh-extra.com/html/siemens/simpro-100/simpro-100_instruction-manual_383121125.webp)
SIMPRO-100
Event Analysis
9
PRIM-2400C
123
9.6.3
Retrieving SER Reports
The relay saves the latest 512 rows of the SER
report in nonvolatile memory.
Row 1 is the most recently triggered row and
Row 512 is the oldest. Use the serial port SER
command to view the SER report by date or SER
row number as outlined in Table 9.6.
Table 9.6
Retrieving SER Reports
The date entries in the previous example SER
commands depend on the Date Format setting
DATE_F. If setting DATE_F is equal to MDY, you
should enter the dates as in the above examples
(Month/Day/Year). If setting DATE_F is equal to
YMD, you should enter the dates Year/Month/
Day. If the requested SER event report rows do
not exist, the relay responds
No SER Data
.
9.6.4
Resetting the SER Report
Buffer
Reset the SER data with the serial port SER R
command.
Example SER
Serial Port
Commands
Format
SER
If you enter the SER command with no numbers following it, the relay displays all available rows, up to row
number 512. The rows display with the oldest row at the beginning (top) of the report and the newest row
(Row 1) at the end (bottom) of the report. Chronological progression through the report is down the page and
in descending row number.
SER 17
If you enter the SER command with a single number following it, the relay displays that number of rows, if they
exist. The rows display with the oldest row at the beginning (top) of the report and the newest row (Row 1) at
the end (bottom) of the report. Chronological progression through the report is down the page and in
descending row number.
SER 10 33
If you enter the SER command with two numbers following it, the relay displays all the rows between (and
including) Rows 10 and 33, if they exist. The rows display with the oldest row (Row 33) at the beginning (top)
of the report and the latest row (Row 10) at the end (bottom) of the report. Chronological progression through
the report is down the page and in descending row number.
SER 47 22
If you enter the SER command with two numbers following it, the relay displays all the rows between (and
including) Rows 47 and 22, if they exist. The rows display with the row (Row 22) at the beginning (top) of the
report and the oldest row (Row 47) at the end (bottom) of the report. Reverse chronological progression
through the report is down the page and in ascending row number.
SER 3/30/97
If you enter the SER command with one date following it, the relay displays all the rows on that date, if they
exist. The rows display with the oldest row at the beginning (top) of the report and the latest row at the end
(bottom) of the report, for the given date. Chronological progression through the report is down the page and
in descending row number.
SER 2/17/97
3/23/97
If you enter the SER command with two dates following it, the relay displays all the rows between (and
including) dates 2/17/97 and 3/23/97, if they exist. The rows display with the oldest row (date 2/17/97) at the
beginning (top) of the report and the latest row (date 3/23/97) at the end (bottom) of the report. Chronological
progression through the report is down the page and in descending row number.
SER 3/16/97
1/5/97
If you enter the SER command with two dates following it, the relay displays all the rows between (and
including) dates 1/5/97 and 3/16/97, if they exist. The rows display with the latest row (date 3/16/97) at the
beginning (top) of the report and the oldest row (date 1/5/97) at the end (bottom) of the report. Reverse
chronological progression through the report is down the page and in ascending row number.
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......