![background image](http://html.mh-extra.com/html/siemens/simpro-100/simpro-100_instruction-manual_383121174.webp)
C
Modbus
™
RTU Communications Protocol
SIMPRO-100
172
PRIM-2400C
0180
Vca Rms Voltage
0 if no voltage option
0
65535
1
0181
Average Rms Voltage
0 if no voltage option
0
65535
1
0182
kW3P Power
0 if no voltage option
-32768
32767
1
0183
kW3P Avg Power
0 if no voltage or single volt
-32768
32767
1
0184
HP
0 if no voltage option
-32768
32767
1
0185
kVAR3P Power
0 if no voltage option
-32768
32767
1
0186
kVA3P Power
0 if no voltage option
-32768
32767
1
0187
Power Factor
0 if no voltage option
-100
100
1
• 0.01
0188
Ig Current
0
65535
1
0189
3I2 Current
0
65535
1
018A
Vg Voltage
0 if no voltage opt or delta
0
65535
1
018B
3V2 Voltage
0 if no voltage option
0
65535
1
018C
System Frequency
2000
7000
1
• 0.01
018D
% Unbalance
0
1000
1
• 0.1
018E
Reserved
018F
Reserved
THERMAL METERING
0190
Temperature Preference
67 = C; 70 = F
67
70
0191
Hottest Winding RTD
See Note 1
See Note 3 See Note 3
1
0192
Hottest Bearing RTD
See Note 1
See Note 3 See Note 3
1
0193
Ambient RTD
See Note 1
See Note 3 See Note 3
1
0194
Hottest Other RTD
See Note 1
See Note 3 See Note 3
1
0195
RTD #1 Temperature
See Note 2
See Note 3 See Note 3
1
0196
RTD #2 Temperature
See Note 2
See Note 3 See Note 3
1
0197
RTD #3 Temperature
See Note 2
See Note 3 See Note 3
1
0198
RTD #4 Temperature
See Note 2
See Note 3 See Note 3
1
0199
RTD #5 Temperature
See Note 2
See Note 3 See Note 3
1
019A
RTD #6 Temperature
See Note 2
See Note 3 See Note 3
1
019B
RTD #7 Temperature
See Note 2
See Note 3 See Note 3
1
019C
RTD #8 Temperature
See Note 2
See Note 3 See Note 3
1
019D
RTD #9 Temperature
See Note 2
See Note 3 See Note 3
1
019E
RTD #10 Temperature
See Note 2
See Note 3 See Note 3
1
019F
RTD #11 Temperature
See Note 2
See Note 3 See Note 3
1
01A0
RTD #12 Temperature
See Note 2
See Note 3 See Note 3
1
01A1
% of FLA
0
65535
1
• 0.1
01A2
% Thermal Capacity
0
65535
1
• 0.1
01A3
RTD % Thermal Capacity
0 if no RTDs available
0
65535
1
01A4
Time to Trip
ss
0
9999
1, 1
01A5
Minutes Since Last Start
0
65535
1
Address
(hex)
Field
Sample
Low
High
Step
Type
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......