![background image](http://html.mh-extra.com/html/siemens/simpro-100/simpro-100_instruction-manual_383121178.webp)
C
Modbus
™
RTU Communications Protocol
SIMPRO-100
176
PRIM-2400C
RTD MAX/MIN METERING
0220
RTD # 1 Max Temperature
FFFFh if reset or no RTD
See Note 3 See Note 3
1
0221
RTD # 1 Max Temperature Date mm, dd (FFFFh if reset)
1, 1
12, 31
1, 1
0222
yyyy (FFFFh if reset)
0
65535
1
0223
RTD # 1 Max Temperature Time hh, mm (FFFFh if reset)
0, 0
23, 59
1, 1
0224
ssss (FFFFh if reset)
0
5999
1
• 0.01
0225
RTD # 1 Min Temperature
FFFFh if reset or no RTD
See Note 3 See Note 3
1
0226
RTD # 1 Min Temperature Date
mm, dd (FFFFh if reset)
1, 1
12, 31
1, 1
0227
yyyy (FFFFh if reset)
0
65535
1
0228
RTD # 1 Min Temperature Time
hh, mm (FFFFh if reset)
0, 0
23, 59
1, 1
0229
ssss (FFFFh if reset)
0
5999
1
• 0.01
022A
RTD # 2 Max Temperature
FFFFh if reset or no RTD
See Note 3 See Note 3
1
022B
RTD # 2 Max Temperature Date mm, dd (FFFFh if reset)
1, 1
12, 31
1, 1
022C
yyyy (FFFFh if reset)
0
65535
1
022D
RTD # 2 Max Temperature Time hh, mm (FFFFh if reset)
0, 0
23, 59
1, 1
022E
ssss (FFFFh if reset)
0
5999
1
• 0.01
022F
RTD # 2 Min Temperature
FFFFh if reset or no RTD
See Note 3 See Note 3
1
0230
RTD # 2 Min Temperature Date
mm, dd (FFFFh if reset)
1, 1
12, 31
1, 1
0231
yyyy (FFFFh if reset)
0
65535
1
0232
RTD # 2 Min Temperature Time
hh, mm (FFFFh if reset)
0, 0
23, 59
1, 1
0233
ssss (FFFFh if reset)
0
5999
1
• 0.01
0234
RTD # 3 Max Temperature
FFFFh if reset or no RTD
See Note 3 See Note 3
1
0235
RTD # 3 Max Temperature Date mm, dd (FFFFh if reset)
1, 1
12, 31
1, 1
0236
yyyy (FFFFh if reset)
0
65535
1
0237
RTD # 3 Max Temperature Time hh, mm (FFFFh if reset)
0, 0
23, 59
1, 1
0238
ssss (FFFFh if reset)
0
5999
1
• 0.01
0239
RTD # 3 Min Temperature
FFFFh if reset or no RTD
See Note 3 See Note 3
1
023A
RTD # 3 Min Temperature Date
mm, dd (FFFFh if reset)
1, 1
12, 31
1, 1
023B
yyyy (FFFFh if reset)
00
65535
1
023C
RTD # 3 Min Temperature Time
hh, mm (FFFFh if reset)
0, 0
23, 59
1, 1
023D
ssss (FFFFh if reset)
0
5999
1
• 0.01
023E
RTD # 4 Max Temperature
FFFFh if reset or no RTD
See Note 3 See Note 3
1
023F
RTD # 4 Max Temperature Date mm, dd (FFFFh if reset)
1, 1
12, 31
1, 1
0240
yyyy (FFFFh if reset)
0
65535
1
0241
RTD # 4 Max Temperature Time hh, mm (FFFFh if reset)
0, 0
23, 59
1, 1
0242
ssss (FFFFh if reset)
0
5999
1
• 0.01
0243
RTD # 4 Min Temperature
FFFFh if reset or no RTD
See Note 3 See Note 3
1
0244
RTD # 4 Min Temperature Date
mm, dd (FFFFh if reset)
1, 1
12, 31
1, 1
0245
yyyy (FFFFh if reset)
0
65535
1
Address
(hex)
Field
Sample
Low
High
Step
Type
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...