![background image](http://html.mh-extra.com/html/siemens/simpro-100/simpro-100_instruction-manual_383121184.webp)
C
Modbus
™
RTU Communications Protocol
SIMPRO-100
182
PRIM-2400C
02FF
Avg Running Current
0
65535
1
0300
Avg Running kW
0 if no voltage option
0
65535
1
0301
Avg Running kVAR In
0 if no voltage option
0
65535
1
0302
Avg Running kVAR Out
0 if no voltage option
0
65535
1
0303
Avg Running kVA
0 if no voltage option
0
65535
1
0304
Avg Hottest Winding RTD Temp
See Note 1
See Note 3 See Note 3
1
0305
Avg Hottest Bearing RTD Temp
See Note 1
See Note 3 See Note 3
1
0306
Avg Ambient RTD Temp
See Note 1
See Note 3 See Note 3
1
0307
Avg Hottest Other RTD Temp
See Note 1
See Note 3 See Note 3
1
0308
Peak Starting Time
seconds
0
65535
1
• 0.01
0309
Peak Starting Current
0
65535
1
030A
Peak Minimum Starting Voltage
0 if no voltage option
0
65535
1
030B
Peak Starting % Therm Cap
0
65535
1
• 0.1
030C
Peak Running % Therm Cap
0
65535
1
• 0.1
030D
Peak RTD % Therm Cap
0
65535
1
030E
Peak Running Current
0
65535
1
030F
Peak Running kW
0 if no voltage option
0
65535
1
0310
Peak Running kVAR In
0 if no voltage option
0
65535
1
0311
Peak Running kVAR Out
0 if no voltage option
0
65535
1
0312
Peak Running kVA In
0 if no voltage option
0
65535
1
0313
Peak Hottest Winding RTD Temp See Note 1
See Note 3 See Note 3
1
0314
Peak Hottest Bearing RTD Temp See Note 1
See Note 3 See Note 3
1
0315
Peak Ambient RTD Temp
See Note 1
See Note 3 See Note 3
1
0316
Peak Hottest Other RTD Temp
See Note 1
See Note 3 See Note 3
1
0317
Stopped Cooling Time
Minutes
0
65535
1
• 0.1
0318
Starting Thermal Capacity
0
65535
1
• 0.1
0319
Thermal Alarm Count
0
65535
1
031A
Locked Rotor Alarm Count
0
65535
1
031B
Load Loss Alarm Count
0
65535
1
031C
Unbalance Current Alarm Count
0
65535
1
031D
Under Power Alarm Count
0
65535
1
031E
Power Factor Alarm Count
0
65535
1
031F
Reactive Power Alarm Count
0
65535
1
0320
RTD Alarm Count
0
65535
1
0321
Total Alarm Count
0
65535
1
0322
Thermal Trip Count
0
65535
1
0323
Locked Rotor Trip Count
0
65535
1
0324
Load Loss Trip Count
0
65535
1
0325
Load Jam Trip Count
0
65535
1
Address
(hex)
Field
Sample
Low
High
Step
Type
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......