![background image](http://html.mh-extra.com/html/siemens/simpro-100/simpro-100_instruction-manual_383121194.webp)
D
SIMPRO-PC Compatibility Features
SIMPRO-100
192
PRIM-2400C
Table D.4
A5C0 Relay Definition Block A5C1 Fast
Meter Configuration Block
In response to the A5D1 request, the
SIMPRO-100 Relay sends the block
shown in Table D.5.
Table D.5
A5D1 Fast Meter Data Block
In response to the A5C2 or A5C3 request, the
SIMPRO-100 Relay sends the block shown in
Table D.6.
00
Analog channel type
FF
Scale factor type
0000
Scale factor offset in Fast Meter message
4F5448000000 Analog channel name (OTH)
[Hottest Other RTD Temp.]
00
Analog channel type
FF
Scale factor type
0000
Scale factor offset in Fast Meter message
All Versions
00
Reserved
checksum
1-byte checksum of all preceding bytes
Data
Description
A5D1
Command
xx
Length (specific value of xx based on relay
model, as shown below)
63 bytes
Base Relay
71 bytes
Relay with RTDs
103 bytes Relay with voltages
111 bytes Relay with RTDs, voltages
1-byte
1 Status Byte
##-bytes
Magnitudes in 4-byte IEEE floating point
numbers (specific value of ## based on relay
model, as shown below)
36 bytes
Base Relay
76 bytes
Relay with voltages
##-bytes
Magnitudes in 2-byte integer (specific value f
## based on relay model, as shown below)
8 bytes
Relay with RTDs
8-bytes
Time stamp
13-bytes
13 Digital banks:
11 Relay Word rows, plus 2 rows for targets
1-byte
Reserved
checksum
1-byte checksum of all preceding bytes
Data
Description
Data
Description
A5C2 or A5C3 Command; Demand (A5C2) or Peak
Demand (A5C3)
xx
Length in bytes (specific value of xx based
on relay model)
78 bytes Base Relay
118 bytes Relay with voltages
01
# of status flag bytes
00
Scale factors in meter message
00
# of scale factors
xx
# of analog input channels (specific value of
xx based on relay model)
6
Base Relay
10
Relay with voltages
01
# of samples per channel
00
# of digital banks
00
# of calculation blocks
0004
Analog channel offset
xxxx
Time stamp offset (specific value of xxxx
based on relay model)
0034
Base Relay
0054
Relay with voltages
FFFF
Digital offset
494100000000 Analog channel name (IA)
02
Analog channel type
FF
Scale factor type
0000
Scale factor offset in Fast Meter message
494200000000 Analog channel name (IB)
02
Analog channel type
FF
Scale factor type
0000
Scale factor offset in Fast Meter message
494300000000 Analog channel name (IC)
02
Analog channel type
FF
Scale factor type
0000
Scale factor offset in Fast Meter message
494E00000000 Analog channel name (IN)
02
Analog channel type
FF
Scale factor type
0000
Scale factor offset in Fast Meter message
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......