![background image](http://html.mh-extra.com/html/siemens/simpro-100/simpro-100_instruction-manual_383121205.webp)
SIMPRO-100
SIMPRO-PC Compatibility Features
D
PRIM-2400C
203
D.11
CME T Command
xxxxxx
Display thermal meter data in compressed ASCII
format by typing
CME T <CR>
. The relay
replaces the items in italics with the actual relay
data.
The SIMPRO-100 Relay sends:
where:
•
"THM CAP(%)" is the thermal model
thermal capacity used in percent.
•
"RTD TC(%)" is the RTD estimated
thermal capacity used in percent.
•
"CALC TIME" is the calculated time to
thermal trip in seconds.
•
"MINUTES" is the number of minutes
since the last motor start.
•
"STARTS" is the number of motor starts in
the past hour.
RTD labels are replaced with “*” if RTDs are not
supported or enabled. RTD locations and
temperature designators are setting dependent.
RTD thermal capacity is reported as 0 if RTDs are
not supported or enabled.
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......